upsset.cgi - Man Page

Web-based UPS administration program

Synopsis

upsset​.cgi

Note

As a CGI program, this should be invoked through your web server​. If you run it from the command line, it will sit there until you give it input resembling a POST request​.

Description

upsset​.cgi is a read-write NUT client which lets you access many administrative functions within the UPS software from your web browser​. You can change settings and invoke instant commands where available​.

For details about configuring some popular web servers to run NUT CGI programs, please see the upsset.conf(5) page​.

Changing Settings

Some UPS hardware allows you to change certain variables to other values​. To see what’s available, pick a UPS from the chooser and select "settings", then select "View" to update the page​.

You should see a list of items with the descriptions on the left side and the possible options or input spaces on the right​. After changing something, be sure to "Save changes" to update the values in your UPS​.

If your UPS doesn’t support any read/write variables, there will be nothing to do on this page​.

Setting values in read/write variables can also be done from the command line with upsrw(8)​.

Instant Commands

Some UPS hardware also has provisions for performing certain actions at the user’s command​. These include battery tests, battery calibration, front panel tests (beep!) and more​. To access this section, do as above, but pick "Commands" as the function​.

If your UPS supports any instant commands, they will be listed in a chooser widget​. Pick the one you like and "Issue command" to make it happen​.

Note

Some dangerous commands like "Turn off load" may not happen right away​. This is a feature, not a bug​.

The apcsmart(8) driver and some others require that you send this command twice within a short window in order to make it happen​. This is to keep you from accidentally killing your systems by picking the wrong one​.

To actually turn off the load, you have to send the command once, then send it again after 3 seconds elapse but before 15 seconds pass​. If you do it too quickly or slowly, you have to wait at least 3 seconds but not 15 seconds again​.

You can also invoke instant commands from the command line with upscmd(8)​.

Access Control

It sends commands and settings via the server upsd(8) to your driver, which manages the hardware for you​. You must use credentials defined in upsd.users(5) file on that data server with appropriate permissions​.

upsset will only talk to upsd(8) servers that have been defined in your hosts.conf(5)​. If it complains about "Access to that host is not authorized", check your hosts​.conf first​.

Security

upsset will not run until you convince it that your CGI directory has been secured​. This is due to the possibility of someone using upsset to try password combinations against your upsd(8) server​.

See the example upsset​.conf file for more information on how you do this​. The short explanation is—if you can’t lock it down, don’t try to run it​.