phoenixcontact_modbus - Man Page

Driver for Phoenix Contact

Synopsis

phoenixcontact_modbus -h

phoenixcontact_modbus -a DEVICE_NAME [OPTIONS]

Note

This man page only documents the hardware-specific features of the phoenixcontact_modbus driver​. For information about the core driver, see nutupsdrv(8)​.

Supported Hardware

This driver should support the PhoenixContact QUINT-UPS industrial DC UPS, model 2320461 and all compatible models​. More information about this UPS can be found among Internet resources below​.

phoenixcontact_modbus uses the libmodbus project, for Modbus implementation​.

How to Configure the Ups

Note: this UPS and its manual refers to Low-Batt as "Shutdown Event"​.

You need the "IFS-RS232-DATACABLE" to communicate with the UPS in Linux as the IFS-USB cable doesn’t seem to be supported​. FYI communication parameters are: 115200,E,8,1​.

You also need the UPS-CONF Windows software (free; download from their site), to configure the UPS signals and timers​.

  1. Run the UPS-CONF
  2. Go to Settings→Time Setting
  3. Choose "state of charge shutdown delay"
  4. Choose Remote starts PC-Shutdown in Mains and Battery mode
  5. On the PC-Shutdown enter the maximum value (5 minutes)
  6. On the PC-Restart delay enter the time you want the UPS to leave the output power off before restarting (e​.g​. 60 seconds), after mains power is restored​.
  7. On the UPS, turn the screw to the "PC-MODE" position

Configuring the above way ensures that:

Meaning of settings:

Extra Arguments

This driver doesn’t support any optional settings​.

Installation

This driver may be not built by default​. You can build it by installing libmodbus and running configure --with-modbus=yes​.

You also need to give proper permissions on the local serial device file (/dev/ttyS0 for example) to allow the NUT user to access it​.

Instant Commands

This driver doesn’t support any instant commands​.

Configurable Variables

The following variables can be set in the NUT configuration as default​.* values to override or monitor UPS behavior using the phoenixcontact_modbus driver​.

Note

As of NUT v2​.8​.4, there is currently no support for run-time setting of these values (e​.g​. with upsrw(8))​. Currently they are only considered once, during driver initialization​.

battery​.energysave​.delay=num

Time after entering battery mode before PC shutdown signal is triggered by the UPS (in seconds)​.

ups​.timer​.shutdown=num

Time allowed for PC to shutdown (in seconds)​. Maximum is 300 seconds​.

ups​.timer​.start=num

Duration for which output power remains turned off before rebooting the PC system back on (in seconds)​.

ups​.delay​.start=num

Delay before switching back to mains after power is restored (in seconds)​. The mains voltage must be within the threshold for this time, to initiate automatic PC restart​.

experimental​.ups​.mode​.selector=num

UPS operating mode​. For example, 9 corresponds to PC-Mode (vendor-defined)​.

experimental​.battery​.warning_soh=num

Battery warning threshold for State of Health, in percent​.

input​.voltage​.low​.critical=num

Threshold voltage (in V) below which the UPS will switch to battery mode​.

input​.voltage​.high​.critical=num

Voltage threshold (in V) above which the UPS will consider mains power restored (see also below)​.

Authors

See Also

The core driver

nutupsdrv(8)

Internet resources

  • The NUT (Network UPS Tools) home page: https://www​.networkupstools​.org/historic/v2​.8​.5/
  • libmodbus home page: http://libmodbus​.org
  • More information about PhoenixContact QUINT-UPS industrial DC UPS, model 2320461 UPS series can be found here: https://www​.phoenixcontact​.com/online/portal/us?uri=pxc-oc-itemdetail:pid=2320461

Info

10/07/2026 Network UPS Tools 2.8.5 NUT Manual